| Model |
LR-SSF-Ⅰ / LR-SSF-Ⅱ |
LR-SLA-Ⅰ / LR-SLA-Ⅱ |
| Fluid |
LPG (Liquefied Petroleum Gas) |
| Capacity (kg/h) |
Max. 300 (100% for propane)
Max. 150 (30% or less for propane)
|
Max. 900 (100% for propane)
Max. 300 (30% or less for propane)
|
| Changeover Pressure (MPa) |
LR-SF-Ⅰ: 0.05 ∼ 0.22
LR-SF-Ⅱ: 0.15 ∼ 0.34
|
LR-LA-Ⅰ: 0.05 ∼ 0.18
LR-LA-Ⅱ: 0.15 ∼ 0.30
|
| Changeover Pressure Operating Accuracy (MPa) |
±0.01 |
| Required Inlet Pressure |
(Changeover pressure +ΔP) ∼ 1.56 MPa |
| LR-SF Capacity (kg/h) |
100 |
150 |
200 |
250 |
300 |
ΔP
(MPa)
|
Type Ⅰ |
0.03 |
0.07 |
0.11 |
0.14 |
0.18 |
| Type Ⅱ |
0.06 |
0.08 |
0.11 |
0.15 |
0.18 |
| LR-LA Capacity (kg/h) |
300 |
450 |
600 |
750 |
900 |
ΔP (MPa) |
LR-LA-Ⅰ |
0.03 |
0.07 |
0.11 |
0.14 |
0.18 |
| LR-LA-Ⅱ |
0.05 |
0.09 |
0.13 |
0.16 |
0.20 |
| Inlet Size |
JIS20K 20A Flange |
JIS20K 25A Flange |
| Outlet Size |
JIS20K 20A Flange |
JIS20K 25A Flange |
| Weight (kg) |
13 |
14 |
Dimensions (mm) (W×H×D) |
215 ×425 ×195 |
260 ×445 ×225 |
| LR Panel (Option) |
Dimensions (mm) (W×H×D) |
90 ×170 ×60 |
| Voltage |
AC100V |
| Alarm Terminal |
100V 5A (Contact material: silver contact plated with gold) |