| Model |
LRU-SSF-Ⅰ / LRU-SSF-Ⅱ |
| Fluid |
LPG (Liquefied Petroleum Gas) |
| Capacity (kg/h) |
Max. 300 (100% for propane)
Max. 150 (30% or less for propane) |
| Changeover Pressure (MPa) |
LR-SF-Ⅰ: 0.05 ∼ 0.22
LR-SF-Ⅱ: 0.15 ∼ 0.34 |
| Changeover Pressure Operating Accuracy (MPa) |
±0.01 |
| Required Inlet Pressure |
(Changeover pressure +ΔP) ∼ 1.56 MPa |
| Capacity (kg/h) |
100 |
150 |
200 |
250 |
300 |
ΔP
(MPa) |
Type Ⅰ |
0.03 |
0.07 |
0.11 |
0.14 |
0.18 |
| Type Ⅱ |
0.06 |
0.08 |
0.11 |
0.15 |
0.18 |
| Inlet Size |
JIS20K 20A Flange |
| Outlet Size |
JIS20K 20A Flange |
| Weight (kg) |
13 |
20 |
Dimensions(mm) (W×H×D) |
215 ×425 ×195 |
385 ×510 ×195 |
| LR Panel (Option) |
Dimensions (mm) (W×H×D) |
90 ×170 ×60 |
| Voltage |
AC100V |
| Alarm Terminal |
100V 5A (Contact material: silver contact plated with gold) |

 |
| ・ |
Explosion-proof Signal Transmitter Switch (Optional)
|
|
With Signal Transmitter Switch, the actuation of LR could be verified under
|
|
remote monitor through a telephone line
|
| ・ |
LPG consumption should be lower than the LR standard capacity indicated above
|
| ・ |
If the LR inlet pressure requirement could not be adapted, it might be necessary to change the LPG composition
|

|